Fault - SG2

Display - AC Surge 2


Description-

AC Surge Protector Failure AC Surge device on TR2 X1/X2/X3 for 208/120- Vac


Resolution-

Replace AC Surge protector SS3 in the AC Cabinet Section


■ Verify 30 A fuses F46 | F47 | F48


■ Verify ckt-wiring SS3-12 – 18RD581 – CAUX3-J3-5


■ Verify ckt-wiring SS3-12 – 18RD3361 – TB10-3 (+24 V)