Warning - DCF2

Display - IDC Over Neg


Description - 

Software Overcurrent detection (negative direction)


Detection of possible miss-wiring in the array where IDC Feedback of any stack exceeds –50 A for 3 seconds.


Resolution-

1. Check inverter re-combiner and DC bus-bar connections


2. Check array wiring external to inverter