Warning - CTF9

Display - K8 Control


Description-

Stack 1 AC contactor (K8) feedback does not match commanded


Resolution-

1. Check K8 contactor auxiliary feedback wiring


2. If first time operating inverter, make sure all factory jumpershave been removed from the contact.


3. Check (series-routed) voltages on coil: 208 Vac L-LK8-A1: TB1-15 - K8-A2: TB1-8

Did you find it helpful? Yes No