Fault - DCF0

Display - Array Low    


Description-

Low irradiance detection.


This is detected when DC Power is less than 7.5 kW or DC Voltage is under minimum PV Vdc for >10 msec.


Resolution-

Normal Operation (No Action Required)


■ Evening transition from power-export to sleep states due to waning irradiance


■ Common in early morning when low irradiance can’t support power-export Abnormal Operation (typically when solar irradiance > 200 W/m2)


■ Verify solar array modules for damage and source and output ckts wiring defects


■ Verify inverter re-combiner, input OCPDs and bus-bar connections

Did you find it helpful? Yes No