Warning - THM16

Display -

Inlet Water Temp


Description - 

Stacks’ Inlet Water Temperature sensor exceeds over-temp threshold (70 °C) for 10 seconds.


Resolution-

Coolant is not sufficiently cooled exiting the radiator


1. Verify Inlet Temp reading on HMI: Monitor menu


2. Check for coolant leaks


3. Check for: blower operation | air-filter blockage or reduction of air-flow thru radiator


4. Check coolant Temperature Sensor/Transducer TT1 in LC cabinet section: wiring


■ TB11-6 | TB11-13 | CANUX2 J7-8/3/(7-shield drain-wire)